EventId
|
SiteName
|
FeederId
|
Phase
|
First Event
|
Last Event
|
Cause
|
Weather
|
Isolation Equipment Code
|
Failed Equipment Code
|
Details
|
| 0001 |
Site0009 |
F_0000065 |
2 |
2005-01-01 10:10:34.487 |
2005-01-01 10:10:39.870 |
Tree |
Clear Weather |
Recloser |
LINE CUT |
Fault caused line recloser lockout. Tree Outside Right of Way (Fall/Lean On Primary) |
| 0004 |
Site0009 |
F_0000065 |
2 |
2005-01-01 10:10:34.487 |
2005-01-01 10:10:39.870 |
Tree |
Clear Weather |
Recloser |
LINE CUT |
Fault caused line recloser lockout. Tree Outside Right of Way (Fall/Lean On Primary) |
| 0005 |
Site0009 |
F_0000065 |
2 |
2005-01-01 10:10:34.487 |
2005-01-01 10:10:39.870 |
Tree |
Clear Weather |
Recloser |
LINE CUT |
Fault caused line recloser lockout. Tree Outside Right of Way (Fall/Lean On Primary) |
| 0007 |
Site0009 |
F_0000065 |
2 |
2005-01-01 10:10:34.487 |
2005-01-01 10:10:39.870 |
Tree |
Clear Weather |
Recloser |
LINE CUT |
Fault caused line recloser lockout. Tree Outside Right of Way (Fall/Lean On Primary) |
| 3042 |
Site0006 |
F_0000041 |
4 |
2005-01-04 03:39:06.000 |
2005-01-04 03:39:06.000 |
Equipment |
Unknown |
Fuse |
Other |
Equipment, Device UG, Damaged. |
| 0021 |
Site0009 |
F_0000061 |
1 |
2005-01-07 19:20:10.599 |
2005-01-07 19:20:10.613 |
Equipment |
Clear Weather |
CO15 |
FUSE |
Overhead Insulator Failure. BROKEN INSULATOR |
| 0022 |
Site0009 |
F_0000061 |
1 |
2005-01-07 19:20:10.599 |
2005-01-07 19:20:10.613 |
Equipment |
Clear Weather |
Fuse CO15 |
FUSE |
Overhead Insulator Failure. BROKEN INSULATOR |
| 0062 |
Site0009 |
F_0000065 |
4 |
2005-01-14 05:39:59.364 |
2005-01-14 05:40:01.198 |
Undetermined |
Raining |
CO15LB |
FUSE |
storm |
| 0064 |
Site0009 |
F_0000065 |
4 |
2005-01-14 05:39:59.364 |
2005-01-14 05:40:01.198 |
Undetermined |
Raining |
CO15LB |
FUSE |
storm |
| 0067 |
Site0009 |
F_0000065 |
4 |
2005-01-14 07:22:52.495 |
2005-01-14 07:22:52.828 |
Tree |
Thunderstorm |
CO15LB |
FUSE |
Tree/Limb Growth |
| 0065 |
Site0009 |
F_0000065 |
4 |
2005-01-14 07:22:52.495 |
2005-01-14 07:22:52.828 |
Tree |
Thunderstorm |
CO15LB |
FUSE |
Tree/Limb Growth |
| 0068 |
Site0009 |
F_0000065 |
2 |
2005-01-14 08:07:18.573 |
2005-01-14 08:07:18.573 |
Tree |
Clear Weather |
|
CUSTOMER |
VINES ON TRANSFORMER |
| 2760 |
Site0010 |
|
1 |
2005-01-18 05:41:21.000 |
2005-01-18 05:41:21.000 |
Unknown |
Unknown |
Unknown |
Unknown |
Short duration variation. No outage information found. |
| 3048 |
Site0012 |
F_0000037 |
3 |
2005-01-25 03:29:36.000 |
2005-01-25 03:29:51.000 |
Equipment |
Unknown |
Breaker |
Capacitor |
Equipment, Capacitor Station, Damaged. |
| 2761 |
Site0010 |
F_0000032 |
4 |
2005-01-30 16:02:34.000 |
2005-01-30 16:02:34.000 |
Equipment |
|
Breaker |
|
A conductor off the pin on the mainline of F_0000032 out of Site0010 Sub caused the circuit breaker to trip. |
| 2762 |
Site0010 |
F_0000029 |
2 |
2005-02-02 15:10:14.000 |
2005-02-02 15:10:14.000 |
Equipment |
|
Breaker |
|
A cable fault on the underground portion of F_0000029 out of Site0010 Sub. caused the circuit breaker to trip. |
| 3067 |
Site0006 |
F_0000041 |
2 |
2005-02-11 06:10:46.000 |
2005-02-11 06:10:46.000 |
Weather |
Wind |
Breaker |
No Damage |
Undetermined, Wind / Weather Related. |
| 0207 |
Site0009 |
F_0000062 |
4 |
2005-02-28 07:49:04.979 |
2005-02-28 07:49:04.979 |
Undetermined |
Snow/Ice |
CO15LB |
FUSE |
snow on limbs into lines |
| 2765 |
Site0010 |
F_0000022 |
2 |
2005-03-05 13:21:43.000 |
2005-03-05 13:21:43.000 |
Equipment |
|
Breaker |
|
A cable fault on the underground portion of F_0000022 out of Site0010 Substation tripped the circuit breaker. |
| 0249 |
Site0009 |
F_0000065 |
4 |
2005-03-08 13:06:09.670 |
2005-03-08 13:06:16.919 |
Tree |
Major Storm |
CO15 |
FUSE |
Tree Outside Right of Way (Fall/Lean On Primary). Tree fell on phase A. |
| 0247 |
Site0009 |
F_0000065 |
4 |
2005-03-08 13:06:09.670 |
2005-03-08 13:06:16.919 |
Tree |
Major Storm |
CO15 |
FUSE |
Tree Outside Right of Way (Fall/Lean On Primary). Tree fell on phase A. |
| 0245 |
Site0009 |
F_0000065 |
4 |
2005-03-08 13:06:09.670 |
2005-03-08 13:06:16.919 |
Tree |
Major Storm |
CO15 |
FUSE |
Tree Outside Right of Way (Fall/Lean On Primary). Tree fell on phase A. |
| 0243 |
Site0009 |
F_0000065 |
4 |
2005-03-08 13:06:09.670 |
2005-03-08 13:06:16.919 |
Tree |
Major Storm |
CO15 |
FUSE |
Tree Outside Right of Way (Fall/Lean On Primary). Tree fell on phase A. |
| 0251 |
Site0009 |
F_0000065 |
1 |
2005-03-08 13:28:22.677 |
2005-03-08 13:28:22.677 |
Tree |
Major Storm |
|
CUSTOMER |
Tree Outside Right of Way (Fall/Lean On Primary). Tore primary line down. |
| 0253 |
Site0009 |
F_0000063 |
1 |
2005-03-08 14:49:09.783 |
2005-03-08 14:49:09.783 |
Tree |
Major Storm |
CO15LB |
FUSE |
Limb Fell from Outside Right of Way |
| 0287 |
Site0009 |
F_0000061 |
5 |
2005-03-17 05:03:51.000 |
2005-03-17 05:04:07.900 |
Vehicle |
Snow/Ice |
SECT200NLB |
SECTIONALIZER |
CAR HIT POLE |
| 0284 |
Site0009 |
F_0000061 |
5 |
2005-03-17 05:03:51.000 |
2005-03-17 05:04:07.900 |
Vehicle |
Snow/Ice |
SECT200NLB |
SECTIONALIZER |
CAR HIT POLE |
| 0283 |
Site0009 |
F_0000061 |
5 |
2005-03-17 05:03:51.000 |
2005-03-17 05:04:07.900 |
Vehicle |
Snow/Ice |
SECT200NLB |
SECTIONALIZER |
CAR HIT POLE |
| 0281 |
Site0009 |
F_0000061 |
5 |
2005-03-17 05:03:51.000 |
2005-03-17 05:04:07.900 |
Vehicle |
Snow/Ice |
SECT200NLB |
SECTIONALIZER |
CAR HIT POLE |
| 0289 |
Site0009 |
F_0000061 |
7 |
2005-03-17 05:58:49.612 |
2005-03-17 05:58:49.612 |
Planned |
Snow/Ice |
OCB |
BREAKER/SWITCH |
Repair/Replace Damaged or Failed Facilities |
| 3127 |
Site0012 |
F_0000037 |
2 |
2005-03-22 18:33:30.000 |
2005-03-22 18:33:30.000 |
Equipment |
Unknown |
Fuse |
Transformer |
Equipment, Transformer UG, Damaged. |
| 0306 |
Site0009 |
F_0000063 |
1 |
2005-03-23 07:21:16.755 |
2005-03-23 07:21:18.505 |
Planned |
Clear Weather |
CO15 |
FUSE |
Repair/Replace Damaged or Failed Facilities |
| 0366 |
Site0009 |
F_0000065 |
2 |
2005-03-28 07:53:48.010 |
2005-03-28 07:53:48.010 |
Equipment |
Thunderstorm |
|
CUSTOMER |
lightning. Cutout/Fuse Link Failure |
| 2771 |
Site0014 |
F_0000012 |
1 |
2005-04-06 15:05:06.000 |
2005-04-06 15:05:06.000 |
Equipment |
|
Breaker |
|
A splice failure on the aerial cable portion of F_0000012 from Site0014 Sub. caused the circuit breaker to trip. |
| 0550 |
Site0009 |
F_0000065 |
2 |
2005-04-20 10:36:17.051 |
2005-04-20 10:36:17.051 |
Equipment |
Clear Weather |
CO15LB |
FUSE |
Fuse was blown, did not see any problems. Loggers at end of road say they did not hit line. |
| 2776 |
Site0010 |
F_0000030 |
4 |
2005-05-06 10:01:38.000 |
2005-05-06 10:01:38.000 |
Equipment |
|
Breaker |
|
A cable fault on the UG lead cable portion of F_0000030 from Site0010 failed. |
| 0713 |
Site0009 |
F_0000063 |
1 |
2005-05-12 20:51:03.016 |
2005-05-12 20:51:03.016 |
Equipment |
Thunderstorm |
CO15 |
FUSE |
Cutout/Fuse Link Failure. lighting in area |
| 0715 |
Site0009 |
F_0000064 |
1 |
2005-05-12 20:59:47.344 |
2005-05-12 20:59:47.344 |
Undetermined |
Thunderstorm |
CO15LB |
FUSE |
|
| 0716 |
Site0009 |
F_0000064 |
1 |
2005-05-13 01:36:09.533 |
2005-05-13 01:36:09.533 |
Tree |
Thunderstorm |
|
CUSTOMER |
Fuse on transformer was blown due to tree limb on trans riser. Tree/Limb Growth |
| 0716 |
Site0009 |
F_0000064 |
1 |
2005-05-13 01:36:09.533 |
2005-05-13 01:36:09.533 |
Tree |
Thunderstorm |
|
CUSTOMER |
Fuse on transformer was blown due to tree limb on trans riser. Tree/Limb Growth |
| 0722 |
Site0009 |
F_0000062 |
4 |
2005-05-15 07:09:03.962 |
2005-05-15 07:09:04.379 |
Animal |
Clear Weather |
CO15LB |
FUSE |
|
| 0719 |
Site0009 |
F_0000062 |
4 |
2005-05-15 07:09:03.962 |
2005-05-15 07:09:04.379 |
Animal |
Clear Weather |
CO15LB |
FUSE |
|
| 0723 |
Site0009 |
F_0000063 |
1 |
2005-05-15 09:19:19.125 |
2005-05-15 09:19:19.125 |
Tree |
Clear Weather |
CO15 |
FUSE |
Tree Inside Right of Way (Fall/Lean On Primary) |
| 0775 |
Site0009 |
F_0000063 |
2 |
2005-05-17 06:33:49.340 |
2005-05-17 06:33:49.340 |
Undetermined |
Clear Weather |
CO15 |
FUSE |
possible riser to close to pole |
| 0803 |
Site0009 |
F_0000063 |
4 |
2005-05-19 04:04:11.465 |
2005-05-19 06:02:52.132 |
Equipment |
Clear Weather |
R100-4E |
RECLOSER |
Overhead Arrester Failure. UNKNOWN CAUSE AT TIME |
| 0807 |
Site0009 |
F_0000063 |
4 |
2005-05-19 04:04:11.465 |
2005-05-19 06:02:52.132 |
Equipment |
Clear Weather |
R100-4E |
RECLOSER |
Overhead Arrester Failure. UNKNOWN CAUSE AT TIME |
| 0804 |
Site0009 |
F_0000063 |
4 |
2005-05-19 04:04:11.465 |
2005-05-19 06:02:52.132 |
Equipment |
Clear Weather |
R100-4E |
RECLOSER |
Overhead Arrester Failure. UNKNOWN CAUSE AT TIME |
| 0781 |
Site0009 |
F_0000063 |
4 |
2005-05-19 04:04:11.465 |
2005-05-19 06:02:52.132 |
Equipment |
Clear Weather |
R100-4E |
RECLOSER |
Overhead Arrester Failure. UNKNOWN CAUSE AT TIME |
| 0782 |
Site0009 |
F_0000063 |
4 |
2005-05-19 04:04:11.465 |
2005-05-19 06:02:52.132 |
Equipment |
Clear Weather |
R100-4E |
RECLOSER |
Overhead Arrester Failure. UNKNOWN CAUSE AT TIME |
| 0785 |
Site0009 |
F_0000063 |
4 |
2005-05-19 04:04:11.465 |
2005-05-19 06:02:52.132 |
Equipment |
Clear Weather |
R100-4E |
RECLOSER |
Overhead Arrester Failure. UNKNOWN CAUSE AT TIME |
| 0788 |
Site0009 |
F_0000063 |
4 |
2005-05-19 04:04:11.465 |
2005-05-19 06:02:52.132 |
Equipment |
Clear Weather |
R100-4E |
RECLOSER |
Overhead Arrester Failure. UNKNOWN CAUSE AT TIME |
| 0790 |
Site0009 |
F_0000063 |
4 |
2005-05-19 04:04:11.465 |
2005-05-19 06:02:52.132 |
Equipment |
Clear Weather |
R100-4E |
RECLOSER |
Overhead Arrester Failure. UNKNOWN CAUSE AT TIME |
| 0793 |
Site0009 |
F_0000063 |
4 |
2005-05-19 04:04:11.465 |
2005-05-19 06:02:52.132 |
Equipment |
Clear Weather |
R100-4E |
RECLOSER |
Overhead Arrester Failure. UNKNOWN CAUSE AT TIME |
| 0796 |
Site0009 |
F_0000063 |
4 |
2005-05-19 04:04:11.465 |
2005-05-19 06:02:52.132 |
Equipment |
Clear Weather |
R100-4E |
RECLOSER |
Overhead Arrester Failure. UNKNOWN CAUSE AT TIME |
| 0799 |
Site0009 |
F_0000063 |
4 |
2005-05-19 04:04:11.465 |
2005-05-19 06:02:52.132 |
Equipment |
Clear Weather |
R100-4E |
RECLOSER |
Overhead Arrester Failure. UNKNOWN CAUSE AT TIME |
| 0801 |
Site0009 |
F_0000063 |
4 |
2005-05-19 04:04:11.465 |
2005-05-19 06:02:52.132 |
Equipment |
Clear Weather |
R100-4E |
RECLOSER |
Overhead Arrester Failure. UNKNOWN CAUSE AT TIME |
| 0779 |
Site0009 |
F_0000063 |
4 |
2005-05-19 04:04:11.465 |
2005-05-19 06:02:52.132 |
Equipment |
Clear Weather |
R100-4E |
RECLOSER |
Overhead Arrester Failure. UNKNOWN CAUSE AT TIME |
| 0809 |
Site0009 |
F_0000063 |
4 |
2005-05-19 06:02:54.949 |
2005-05-19 06:03:25.782 |
Equipment |
Clear Weather |
|
SERVICE TRANSFORMER |
Overhead Transformer Outage |
| 0811 |
Site0009 |
F_0000063 |
4 |
2005-05-19 06:02:55.000 |
2005-05-19 06:03:25.782 |
Equipment |
Clear Weather |
|
SERVICE TRANSFORMER |
Overhead Transformer Outage |
| 0852 |
Site0009 |
F_0000063 |
2 |
2005-05-24 16:41:55.486 |
2005-05-24 16:41:55.903 |
Lightning |
Thunderstorm |
CO15 |
FUSE |
Lightning struck transf, burned primary down.Overhead Primary Failure (No Tree Involved) |
| 0855 |
Site0009 |
F_0000063 |
2 |
2005-05-24 16:41:55.486 |
2005-05-24 16:41:55.903 |
Lightning |
Thunderstorm |
CO15 |
FUSE |
Lightning struck transf, burned primary down.Overhead Primary Failure (No Tree Involved) |
| 0857 |
Site0009 |
F_0000061 |
1 |
2005-05-24 23:29:42.558 |
2005-05-24 23:29:43.000 |
Equipment |
Windy |
CO15 |
FUSE |
Cutout/Fuse Link Failure. possible lightning |
| 0859 |
Site0009 |
F_0000061 |
1 |
2005-05-25 07:29:30.345 |
2005-05-25 07:29:30.345 |
Equipment |
Clear Weather |
CO15 |
FUSE |
Overhead Transformer Outage. Bblown tap line fuse bad transformer. |
| 0868 |
Site0009 |
F_0000065 |
2 |
2005-05-28 08:06:21.811 |
2005-05-28 08:06:21.811 |
Tree |
Clear Weather |
R100E |
RECLOSER |
Tree/Limb Growth |
| 0947 |
Site0009 |
F_0000065 |
2 |
2005-06-05 12:31:11.868 |
2005-06-05 12:31:40.001 |
Customer Request |
Clear Weather |
|
CUSTOMER |
CALL BACK - Lights on. |
| 0942 |
Site0009 |
F_0000065 |
2 |
2005-06-05 12:31:11.868 |
2005-06-05 12:31:40.001 |
Customer Request |
Clear Weather |
|
CUSTOMER |
CALL BACK - Lights on. |
| 0940 |
Site0009 |
F_0000065 |
2 |
2005-06-05 12:31:11.868 |
2005-06-05 12:31:40.001 |
Customer Request |
Clear Weather |
|
CUSTOMER |
CALL BACK - Lights on. |
| 0935 |
Site0009 |
F_0000065 |
2 |
2005-06-05 12:31:11.868 |
2005-06-05 12:31:40.001 |
Customer Request |
Clear Weather |
|
CUSTOMER |
CALL BACK - Lights on. |
| 0952 |
Site0009 |
F_0000065 |
4 |
2005-06-05 17:01:44.427 |
2005-06-05 17:01:44.427 |
Equipment |
Clear Weather |
CO15LB |
FUSE |
Underground Transformer Outage. Need to replace trans. |
| 0962 |
Site0009 |
F_0000065 |
3 |
2005-06-05 22:58:58.707 |
2005-06-06 00:05:04.522 |
Animal |
Clear Weather |
R-OVR-1PT |
RECLOSER |
SNAKE |
| 0957 |
Site0009 |
F_0000065 |
3 |
2005-06-05 22:58:58.707 |
2005-06-06 00:05:04.522 |
Animal |
Clear Weather |
R-OVR-1PT |
RECLOSER |
SNAKE |
| 0960 |
Site0009 |
F_0000065 |
3 |
2005-06-05 22:58:58.707 |
2005-06-06 00:05:04.522 |
Animal |
Clear Weather |
R-OVR-1PT |
RECLOSER |
SNAKE |
| 0963 |
Site0009 |
F_0000065 |
3 |
2005-06-05 22:58:58.707 |
2005-06-06 00:05:04.522 |
Animal |
Clear Weather |
R-OVR-1PT |
RECLOSER |
SNAKE |
| 0965 |
Site0009 |
F_0000065 |
3 |
2005-06-05 22:58:58.707 |
2005-06-06 00:05:04.522 |
Animal |
Clear Weather |
R-OVR-1PT |
RECLOSER |
SNAKE |
| 0959 |
Site0009 |
F_0000065 |
3 |
2005-06-05 22:58:58.707 |
2005-06-06 00:05:04.522 |
Animal |
Clear Weather |
R-OVR-1PT |
RECLOSER |
SNAKE |
| 2778 |
Site0010 |
F_0000024 |
6 |
2005-06-07 15:12:33.000 |
2005-06-07 15:12:33.000 |
Equipment |
|
Breaker |
|
A fault on the riser splice of F_0000024 out of Site0010 tripped the breaker at the substation. |
| 1057 |
Site0009 |
F_0000064 |
1 |
2005-06-09 12:23:23.625 |
2005-06-09 12:23:23.625 |
Equipment |
Clear Weather |
|
SERVICE TRANSFORMER |
Overhead Transformer Outage. CAUSE NOT KNOWN |
| 3152 |
Site0006 |
F_0000041 |
2 |
2005-06-13 18:39:58.000 |
2005-06-13 18:39:58.000 |
Equipment |
Unknown |
Fuse |
Transformer |
Equipment, Transformer UG, Damaged. |
| 3153 |
Site0006 |
F_0000039 |
6 |
2005-06-14 11:46:21.000 |
2005-06-14 11:46:21.000 |
Vehicle |
Unknown |
Fuse |
Pole |
Motor Vehicle, Pole OH, Down. |
| 1088 |
Site0009 |
F_0000065 |
1 |
2005-06-14 15:09:11.550 |
2005-06-14 15:09:11.550 |
Vehicle |
Clear Weather |
|
CUSTOMER |
car hit guy wire |
| 1089 |
Site0009 |
F_0000062 |
2 |
2005-06-14 19:20:06.146 |
2005-06-14 19:20:06.564 |
Animal |
Clear Weather |
CO15LB |
FUSE |
squirrl |
| 1106 |
Site0009 |
F_0000061 |
1 |
2005-06-16 15:37:29.702 |
2005-06-16 15:37:29.702 |
Equipment |
Clear Weather |
CO15LB |
FUSE |
Cutout/Fuse Link Failure |
| 1108 |
Site0009 |
F_0000061 |
1 |
2005-06-17 06:16:34.960 |
2005-06-17 06:16:35.343 |
Animal |
Clear Weather |
|
SERVICE TRANSFORMER |
SNAKE ON LIGHTNING ARRESTER |
| 1111 |
Site0009 |
F_0000061 |
1 |
2005-06-17 06:16:34.960 |
2005-06-17 06:16:35.343 |
Animal |
Clear Weather |
|
SERVICE TRANSFORMER |
SNAKE ON LIGHTNING ARRESTER |
| 3164 |
Site0012 |
F_0000037 |
7 |
2005-06-28 01:24:53.000 |
2005-06-28 01:25:33.000 |
Vehicle |
Unknown |
Breaker |
Pole |
Motor Vehicle, Pole OH, Contact. |
| 3163 |
Site0012 |
F_0000037 |
7 |
2005-06-28 01:24:53.000 |
2005-06-28 01:25:33.000 |
Vehicle |
Unknown |
Breaker |
Pole |
Motor Vehicle, Pole OH, Contact. |
| 3162 |
Site0012 |
F_0000037 |
7 |
2005-06-28 01:24:53.000 |
2005-06-28 01:25:33.000 |
Vehicle |
Unknown |
Breaker |
Pole |
Motor Vehicle, Pole OH, Contact. |
| 3168 |
Site0012 |
F_0000037 |
7 |
2005-06-28 01:24:53.000 |
2005-06-28 01:25:33.000 |
Vehicle |
Unknown |
Breaker |
Pole |
Motor Vehicle, Pole OH, Contact. |
| 3166 |
Site0012 |
F_0000037 |
7 |
2005-06-28 01:24:53.000 |
2005-06-28 01:25:33.000 |
Vehicle |
Unknown |
Breaker |
Pole |
Motor Vehicle, Pole OH, Contact. |
| 1196 |
Site0009 |
F_0000061 |
4 |
2005-06-28 15:39:42.105 |
2005-06-28 15:39:42.105 |
Customer Request |
Clear Weather |
|
CUSTOMER |
custmer called back light on. Customer Breaker / Equipment Failure |
| 2784 |
Site0014 |
F_0000018 |
4 |
2005-07-14 12:25:31.000 |
2005-07-14 12:25:31.000 |
Equipment |
|
Breaker |
|
A terminator failure on the cable dip for the Rt. 8 over pass caused the circuit breaker of F_0000018 to trip |
| 3189 |
Site0012 |
F_0000037 |
7 |
2005-07-16 01:25:46.000 |
2005-07-16 01:26:05.000 |
Vehicle |
Unknown |
Sectionalizer |
Pole |
Motor Vehicle, Pole OH, Damaged. |
| 3187 |
Site0012 |
F_0000037 |
7 |
2005-07-16 01:25:46.000 |
2005-07-16 01:26:05.000 |
Vehicle |
Unknown |
Sectionalizer |
Pole |
Motor Vehicle, Pole OH, Damaged. |
| 3186 |
Site0012 |
F_0000037 |
7 |
2005-07-16 01:25:46.000 |
2005-07-16 01:26:05.000 |
Vehicle |
Unknown |
Sectionalizer |
Pole |
Motor Vehicle, Pole OH, Damaged. |
| 3188 |
Site0012 |
F_0000037 |
7 |
2005-07-16 01:25:46.000 |
2005-07-16 01:26:05.000 |
Vehicle |
Unknown |
Sectionalizer |
Pole |
Motor Vehicle, Pole OH, Damaged. |
| 3235 |
Site0006 |
|
7 |
2005-07-23 04:33:08.000 |
2005-07-23 04:33:08.000 |
Unknown |
Unknown |
Unknown |
Unknown |
Unknown. |
| 2786 |
Site0014 |
|
4 |
2005-07-27 16:55:35.000 |
2005-07-27 16:55:35.000 |
Lightning |
Major Storm |
Unknown |
|
Lightning on the transmission system outside of Utility territory caused a SARFI70 sag at Site0010. |
| 2787 |
Site0010 |
|
4 |
2005-07-27 16:55:35.000 |
2005-07-27 16:55:35.000 |
Lightning |
Major Storm |
Unknown |
|
Lightning on the transmission system outside of Uutility territory caused a SARFI70 sag at Site0010. |
| 2788 |
Site0014 |
|
1 |
2005-07-27 17:08:27.000 |
2005-07-27 17:08:27.000 |
Lightning |
|
Breaker |
|
Lightning on the Line |
| 2789 |
Site0010 |
|
1 |
2005-07-27 17:08:27.000 |
2005-07-27 17:08:27.000 |
Lightning |
|
Breaker |
|
Lightning on the Line |
| 2792 |
Site0014 |
|
2 |
2005-08-14 14:52:33.000 |
2005-08-14 14:52:33.000 |
Lightning |
Major Storm |
Breaker |
|
Lightning during a major storm caused the Site0010 Line breaker to trip and reclose at the substation. There were no outages associated with this event. |
| 2791 |
Site0010 |
|
2 |
2005-08-14 14:52:33.000 |
2005-08-14 14:52:33.000 |
Lightning |
Major Storm |
Breaker |
|
Lightning during a major storm caused the Site0010 Line breaker to trip and reclose at the substation. There were no outages associated with this event. |
| 3296 |
Site0006 |
F_0000041 |
2 |
2005-08-20 09:32:24.000 |
2005-08-20 09:32:24.000 |
Equipment |
Unknown |
Fuse |
Cable |
Equipment, Cable UG, Damaged. (Dig in) |
| 2795 |
Site0010 |
F_0000022 |
3 |
2005-08-21 22:17:41.000 |
2005-08-21 22:17:41.000 |
Equipment |
|
Breaker |
|
A lightning arrester failure caused primary wire to fall to the ground and trip the circuit breaker. |
| 2797 |
Site0010 |
|
4 |
2005-08-30 05:47:25.000 |
2005-08-30 05:47:25.000 |
Unknown |
|
Unknown |
|
Unknown Cause. No outage report was found for this event. |
| 3298 |
Site0006 |
F_0000041 |
2 |
2005-09-05 01:35:38.000 |
2005-09-05 01:36:04.000 |
Equipment |
Unknown |
Fuse |
Cable |
Equipment, Cable UG, Damaged. |
| 2802 |
Site0014 |
|
7 |
2005-09-17 16:20:27.000 |
2005-09-17 16:20:27.000 |
Unknown |
Major Storm |
Breaker |
|
A fault on Transmission Line during a thunderstorm caused a SARFI 70 sag at Site0010 and Site0014 Substation. |
| 2803 |
Site0010 |
|
7 |
2005-09-17 16:20:27.000 |
2005-09-17 16:20:27.000 |
Unknown |
Major Storm |
Breaker |
|
A fault on Transmission Line during a thunderstorm caused a SARFI 70 sag at Site0010 and Site0014 Substation. |
| 3326 |
Site0012 |
|
7 |
2005-09-20 00:51:18.000 |
2005-09-20 00:51:18.000 |
Unknown |
Lightning |
Unknown |
Unknown |
Unknown. |
| 3402 |
Site0005 |
|
6 |
2005-09-26 14:17:46.000 |
2005-09-26 14:17:46.000 |
Unknown |
Unknown |
Unknown |
Unknown |
Unknown. |
| 2811 |
Site0014 |
|
7 |
2005-09-29 09:35:31.000 |
2005-09-29 09:35:31.000 |
Unknown |
|
Breaker |
|
A fault caused breakers to trip and caused SARFI 70 events at Substations. |
| 2812 |
Site0010 |
|
7 |
2005-09-29 09:35:31.000 |
2005-09-29 09:35:31.000 |
Unknown |
|
Breaker |
|
A fault caused breakers to trip and caused SARFI 70 events at Substations. |
| 3403 |
Site0006 |
F_0000041 |
1 |
2005-09-30 10:31:31.279 |
2005-09-30 10:31:37.113 |
Equipment |
Unknown |
Fuse |
Cable |
Equipment, Cable UG, Dig-in. |
| 3404 |
Site0006 |
F_0000041 |
2 |
2005-09-30 10:31:31.279 |
2005-09-30 10:31:37.113 |
Equipment |
Unknown |
Fuse |
Cable |
Equipment, Cable UG, Dig-in. |
| 2813 |
Site0014 |
|
7 |
2005-10-08 04:57:29.000 |
2005-10-08 04:57:29.000 |
Unknown |
|
Breaker |
|
Unknown cause. No outage reported for this event. Short duration, possible recloser operation. Cause incoming to open at the substation due to fault current over 10,000 Amps. |
| 3425 |
Site0006 |
F_0000041 |
1 |
2005-10-18 23:06:49.000 |
2005-10-18 23:07:40.000 |
Undetermined |
Unknown |
Sectionalizer |
No Damage |
Undetermined ? Under Investigation. |
| 3426 |
Site0006 |
F_0000041 |
1 |
2005-10-18 23:06:49.000 |
2005-10-18 23:07:40.000 |
Undetermined |
Unknown |
Sectionalizer |
No Damage |
Undetermined ? Under Investigation. |
| 3427 |
Site0006 |
F_0000041 |
1 |
2005-10-18 23:06:49.000 |
2005-10-18 23:07:40.000 |
Undetermined |
Unknown |
Sectionalizer |
No Damage |
Undetermined ? Under Investigation. |
| 3428 |
Site0006 |
F_0000041 |
1 |
2005-10-18 23:25:28.000 |
2005-10-18 23:25:35.000 |
Undetermined |
Unknown |
Sectionalizer |
No Damage |
Undetermined ? Under Investigation. |
| 3429 |
Site0006 |
F_0000041 |
1 |
2005-10-18 23:25:28.000 |
2005-10-18 23:25:35.000 |
Undetermined |
Unknown |
Sectionalizer |
No Damage |
Undetermined ? Under Investigation. |
| 3430 |
Site0006 |
F_0000041 |
1 |
2005-10-18 23:25:28.000 |
2005-10-18 23:25:35.000 |
Undetermined |
Unknown |
Sectionalizer |
No Damage |
Undetermined ? Under Investigation. |
| 3431 |
Site0006 |
F_0000041 |
1 |
2005-10-19 01:34:21.000 |
2005-10-19 01:34:21.000 |
Undetermined |
Unknown |
Sectionalizer |
No Damage |
Undetermined ? Under Investigation. |
| 3432 |
Site0006 |
F_0000039 |
1 |
2005-10-19 11:37:54.000 |
2005-10-19 11:37:54.000 |
Undetermined |
Unknown |
Service Restorer |
No Damage |
Undetermined. |
| 3433 |
Site0005 |
F_0000003 |
7 |
2005-10-20 12:19:12.000 |
2005-10-20 12:19:12.000 |
Vehicle |
Unknown |
Fuse |
Pole |
Motor Vehicle, Pole OH, Damaged. |
| 3435 |
Site0006 |
F_0000041 |
1 |
2005-10-22 03:17:24.000 |
2005-10-22 03:18:17.000 |
Vehicle |
Unknown |
Sectionalizer |
Fuse Cabinet |
Motor Vehicle, Fuse UG, Damaged |
| 3436 |
Site0006 |
F_0000041 |
1 |
2005-10-22 03:17:24.000 |
2005-10-22 03:18:17.000 |
Vehicle |
Unknown |
Sectionalizer |
Fuse Cabinet |
Motor Vehicle, Fuse UG, Damaged |
| 3437 |
Site0006 |
F_0000041 |
1 |
2005-10-22 03:17:24.000 |
2005-10-22 03:18:17.000 |
Vehicle |
Unknown |
Sectionalizer |
Fuse Cabinet |
Motor Vehicle, Fuse UG, Damaged |
| 3434 |
Site0006 |
F_0000041 |
1 |
2005-10-22 03:17:24.000 |
2005-10-22 03:18:17.000 |
Vehicle |
Unknown |
Sectionalizer |
Fuse Cabinet |
Motor Vehicle, Fuse UG, Damaged |
| 2825 |
Site0010 |
|
7 |
2005-11-09 22:15:44.000 |
2005-11-09 22:15:44.000 |
Lightning |
|
Breaker |
|
Lightning outside of Utility territory on transmission line caused voltage sags across our territory. |
| 2826 |
Site0014 |
|
7 |
2005-11-09 22:15:44.000 |
2005-11-09 22:15:44.000 |
Lightning |
|
Breaker |
|
Lightning outside of Utility territory on transmission line caused voltage sags across our territory. |
| 3449 |
Site0011 |
F_0000033 |
5 |
2005-11-12 18:59:06.000 |
2005-11-12 18:59:06.000 |
Undetermined |
Unknown |
Breaker |
No Damage |
Undetermined. |
| 2827 |
Site0010 |
F_0000024 |
2 |
2005-11-20 15:34:19.000 |
2005-11-20 15:34:19.000 |
Equipment |
|
Breaker |
|
A cable fault on the UG lead cable portion of F_0000024 caused the circuit breaker to trip at Site0010 Substation. |
| 3455 |
Site0012 |
F_0000009 |
3 |
2005-12-06 08:21:51.000 |
2005-12-06 08:21:53.000 |
Equipment |
Unknown |
Fuse |
Cable |
De-Energized For Safety-Equipment, Cable UG, Dig-In. |
| 3456 |
Site0012 |
F_0000009 |
3 |
2005-12-06 08:21:51.000 |
2005-12-06 08:21:53.000 |
Equipment |
Unknown |
Fuse |
Cable |
De-Energized For Safety-Equipment, Cable UG, Dig-In. |
| 3460 |
Site0006 |
F_0000041 |
4 |
2005-12-10 03:13:42.000 |
2005-12-10 03:14:33.000 |
Vehicle |
Unknown |
Breaker |
Other |
Motor Vehicle, Terminator UG, Damaged. |
| 3457 |
Site0006 |
F_0000041 |
4 |
2005-12-10 03:13:42.000 |
2005-12-10 03:14:33.000 |
Vehicle |
Unknown |
Breaker |
Other |
Motor Vehicle, Terminator UG, Damaged. |
| 3458 |
Site0006 |
F_0000041 |
4 |
2005-12-10 03:13:42.000 |
2005-12-10 03:14:33.000 |
Vehicle |
Unknown |
Breaker |
Other |
Motor Vehicle, Terminator UG, Damaged. |
| 3459 |
Site0006 |
F_0000041 |
4 |
2005-12-10 03:13:42.000 |
2005-12-10 03:14:33.000 |
Vehicle |
Unknown |
Breaker |
Other |
Motor Vehicle, Terminator UG, Damaged. |
| 2828 |
Site0010 |
F_0000023 |
2 |
2005-12-18 15:19:10.000 |
2005-12-18 15:19:10.000 |
Equipment |
|
Switch |
Cable |
Cable fault at Loc. 271 tripped a fault interrupter at Loc.260. F_0000023 out of Site0010 Substation. |
| 3472 |
Site0006 |
|
3 |
2006-01-04 14:18:06.000 |
2006-01-04 14:18:06.000 |
Unknown |
Unknown |
Unknown |
Unknown |
Unknonw. |
| 3473 |
Site0006 |
|
3 |
2006-01-04 14:18:06.000 |
2006-01-04 14:18:06.000 |
Unknown |
Unknown |
Unknown |
Unknown |
Unknonw. |
| 2831 |
Site0014 |
|
4 |
2006-01-15 01:00:18.000 |
2006-01-15 01:00:18.000 |
Tree |
Major Storm |
Breaker |
|
Possible tree contact on Transmission Line during a Major windstorm. |
| 2830 |
Site0010 |
|
4 |
2006-01-15 01:00:18.000 |
2006-01-15 01:00:18.000 |
Tree |
Major Storm |
Breaker |
|
Possible tree contact on Transmission Line during a Major windstorm. |
| 3498 |
Site0006 |
F_0000041 |
3 |
2006-01-24 05:32:36.000 |
2006-01-24 05:32:36.000 |
Undetermined |
Wind |
Fuse |
No Damage |
Undeterminde, Possible High Winds. |
| 3557 |
Site0006 |
F_0000038 |
3 |
2006-02-12 12:28:39.000 |
2006-02-12 12:28:51.000 |
Undetermined |
Unknown |
Breaker |
No Damage |
Undetermined. |
| 3555 |
Site0006 |
F_0000038 |
3 |
2006-02-12 12:28:39.000 |
2006-02-12 12:28:51.000 |
Undetermined |
Unknown |
Breaker |
No Damage |
Undetermined. |
| 3554 |
Site0006 |
F_0000038 |
3 |
2006-02-12 12:28:39.000 |
2006-02-12 12:28:51.000 |
Undetermined |
Unknown |
Breaker |
No Damage |
Undetermined. |
| 3553 |
Site0006 |
F_0000038 |
3 |
2006-02-12 12:28:39.000 |
2006-02-12 12:28:51.000 |
Undetermined |
Unknown |
Breaker |
No Damage |
Undetermined. |
| 3552 |
Site0006 |
F_0000038 |
3 |
2006-02-12 12:28:39.000 |
2006-02-12 12:28:51.000 |
Undetermined |
Unknown |
Breaker |
No Damage |
Undetermined. |
| 3556 |
Site0006 |
F_0000038 |
3 |
2006-02-12 12:28:39.000 |
2006-02-12 12:28:51.000 |
Undetermined |
Unknown |
Breaker |
No Damage |
Undetermined. |
| 2842 |
Site0010 |
F_0000023 |
1 |
2006-02-26 14:58:24.000 |
2006-02-26 14:58:24.000 |
Other |
|
Recloser |
|
Mylar ballons got across the primary and tripped a recloser on F_0000023 out of Site0010 Substation. |
| 3577 |
Site0005 |
F_0000004 |
2 |
2006-02-27 22:21:22.000 |
2006-02-27 22:21:22.000 |
Tree |
Unknown |
Fuse |
Transformer |
Tree/Vegetation, XFMR OH, Damaged. |
| 2846 |
Site0014 |
|
7 |
2006-03-17 11:14:34.000 |
2006-03-17 11:28:03.000 |
Equipment |
|
Breaker |
Load tap changer |
Bulk Transformer B Load Tap Changer failed at Site0014 Substation causing a bus outage and complete station outage for five minutes and 10 seconds. |
| 21831 |
Site0002 |
F_0000044 |
1 |
2006-04-18 23:14:23.000 |
2006-04-18 23:14:23.000 |
|
|
|
|
transformer died under t3309 |
| 21832 |
Site0002 |
F_0000044 |
1 |
2006-04-18 23:14:23.000 |
2006-04-18 23:14:23.000 |
Lightning |
|
|
|
lightning caused this fuse to blow |
| 2850 |
Site0014 |
|
5 |
2006-04-19 15:01:48.000 |
2006-04-19 15:01:50.000 |
Other |
|
Breaker |
|
Smoke from a small brush fire caused a line to line fault, tripping breakers at Substations. |
| 2849 |
Site0010 |
|
5 |
2006-04-19 15:01:48.000 |
2006-04-19 15:01:50.000 |
Other |
|
Breaker |
|
Smoke from a small brush fire caused a line to line fault, tripping breakers at Substations. |
| 21833 |
Site0002 |
F_0000046 |
4 |
2006-05-05 02:57:19.000 |
2006-05-05 02:57:19.000 |
Tree |
|
|
|
vines caused this outage under t82 |
| 3730 |
Site0006 |
F_0000041 |
1 |
2006-05-06 14:36:47.000 |
2006-05-06 14:36:47.000 |
Equipment |
Unknown |
Fuse |
Other |
Equipment, Device UG, Damaged. |
| 21834 |
Site0003 |
F_0000049 |
6 |
2006-05-10 11:47:10.000 |
2006-05-10 11:47:10.000 |
|
|
|
|
bad wind storm primary on ground u |
| 3738 |
Site0006 |
F_0000041 |
1 |
2006-05-15 02:47:38.000 |
2006-05-15 02:47:38.000 |
Equipment |
Unknown |
Fuse |
Cable |
Equipment, Cable UG, Damaged. |
| 2857 |
Site0010 |
|
7 |
2006-05-19 14:44:57.000 |
2006-05-19 14:44:57.000 |
Lightning |
Lightning |
Breaker |
|
Simulteneaus lightning on lines during a lightning storm. Both Substations experienced a temporary interruption of 5 seconds. |
| 2856 |
Site0014 |
|
7 |
2006-05-19 14:44:57.000 |
2006-05-19 14:44:57.000 |
Lightning |
Lightning |
Breaker |
|
Simulteneaus lightning on lines during a lightning storm. Both Substations experienced a temporary interruption of 5 seconds. |
| 3740 |
Site0012 |
F_0000037 |
3 |
2006-05-22 04:31:30.000 |
2006-05-22 04:31:30.000 |
Tree |
Wind |
Breaker |
No Damage |
Tree-Weather-Storm, Device OH, Contact. |
| 3742 |
Site0012 |
F_0000037 |
3 |
2006-05-22 04:53:56.000 |
2006-05-22 04:53:56.000 |
Tree |
Wind |
Breaker |
No Damage |
Tree-Weather-Storm, Device OH, Contact. |
| 3745 |
Site0012 |
F_0000037 |
3 |
2006-05-22 05:00:30.000 |
2006-05-22 05:00:58.000 |
Tree |
Wind |
Breaker |
No Damage |
Tree-Weather-Storm, Device OH, Contact. |
| 3746 |
Site0012 |
F_0000037 |
3 |
2006-05-22 05:00:30.000 |
2006-05-22 05:00:58.000 |
Tree |
Wind |
Breaker |
No Damage |
Tree-Weather-Storm, Device OH, Contact. |
| 3744 |
Site0012 |
F_0000037 |
3 |
2006-05-22 05:00:30.000 |
2006-05-22 05:00:58.000 |
Tree |
Wind |
Breaker |
No Damage |
Tree-Weather-Storm, Device OH, Contact. |
| 3761 |
Site0012 |
F_0000009 |
3 |
2006-06-02 04:17:13.000 |
2006-06-02 04:17:43.000 |
Equipment |
Unknown |
Breaker |
TEE |
Equipment, Other Connector UG, Damaged. |
| 3767 |
Site0012 |
F_0000009 |
3 |
2006-06-02 04:17:13.000 |
2006-06-02 04:17:43.000 |
Equipment |
Unknown |
Breaker |
TEE |
Equipment, Other Connector UG, Damaged. |
| 3762 |
Site0012 |
F_0000009 |
3 |
2006-06-02 04:17:13.000 |
2006-06-02 04:17:43.000 |
Equipment |
Unknown |
Breaker |
TEE |
Equipment, Other Connector UG, Damaged. |
| 3765 |
Site0012 |
F_0000009 |
3 |
2006-06-02 04:17:13.000 |
2006-06-02 04:17:43.000 |
Equipment |
Unknown |
Breaker |
TEE |
Equipment, Other Connector UG, Damaged. |
| 3766 |
Site0012 |
F_0000009 |
3 |
2006-06-02 04:17:13.000 |
2006-06-02 04:17:43.000 |
Equipment |
Unknown |
Breaker |
TEE |
Equipment, Other Connector UG, Damaged. |
| 3776 |
Site0006 |
F_0000041 |
4 |
2006-06-03 15:27:01.000 |
2006-06-03 15:27:08.000 |
Equipment |
Unknown |
Sectionalizer |
Transformer |
Equipment, XFMR UG, Damaged. |
| 3775 |
Site0006 |
F_0000041 |
4 |
2006-06-03 15:27:01.000 |
2006-06-03 15:27:08.000 |
Equipment |
Unknown |
Sectionalizer |
Transformer |
Equipment, XFMR UG, Damaged. |
| 3778 |
Site0006 |
F_0000041 |
4 |
2006-06-03 17:57:41.000 |
2006-06-03 17:57:41.000 |
Equipment |
Unknown |
Sectionalizer |
Transformer |
Equipment, XFMR UG, Damaged. |
| 2861 |
Site0014 |
F_0000010 |
4 |
2006-06-09 00:36:14.000 |
2006-06-09 00:36:14.000 |
Unknown |
|
Recloser |
|
Recloser tripped on F_0000010 no apparent cause. |
| 3816 |
Site0012 |
F_0000009 |
6 |
2006-06-21 06:06:42.000 |
2006-06-21 06:06:42.000 |
Equipment |
Unknown |
Fuse |
Pole |
Equipment, Pole OH, Down. |
| 21835 |
Site0003 |
F_0000049 |
2 |
2006-06-21 19:11:36.000 |
2006-06-21 19:11:36.000 |
|
|
|
|
bad transformer under t5063 |
| 3843 |
Site0005 |
|
7 |
2006-06-24 06:37:52.000 |
2006-06-24 06:37:52.000 |
Weather |
Lightning |
Breaker |
No Damage |
Weather Related, Storm, Lightning. |
| 3845 |
Site0012 |
F_0000037 |
7 |
2006-06-24 07:11:05.000 |
2006-06-24 07:11:05.000 |
Weather |
Lightning |
Service Restorer |
No Damage |
Weather Related, Storm, Lightning. |
| 2867 |
Site0010 |
|
2 |
2006-06-28 07:17:20.000 |
2006-06-28 07:17:24.000 |
Tree |
|
Breaker |
|
A tree contact on Transmission Line caused all the line terminals to trip and reclose. |
| 2868 |
Site0014 |
|
2 |
2006-06-28 07:17:20.000 |
2006-06-28 07:17:24.000 |
Tree |
|
Breaker |
|
A tree contact on Transmission Line caused all the line terminals to trip and reclose. |
| 3894 |
Site0006 |
F_0000039 |
4 |
2006-06-29 15:46:03.000 |
2006-06-29 15:46:22.000 |
Tree |
Wind |
Fuse |
No Damage |
Tree/Vegetation, Wire OH, Involved. |
| 3893 |
Site0006 |
F_0000039 |
4 |
2006-06-29 15:46:03.000 |
2006-06-29 15:46:22.000 |
Tree |
Wind |
Fuse |
No Damage |
Tree/Vegetation, Wire OH, Involved. |
| 3895 |
Site0006 |
F_0000039 |
4 |
2006-06-29 15:46:03.000 |
2006-06-29 15:46:22.000 |
Tree |
Wind |
Fuse |
No Damage |
Tree/Vegetation, Wire OH, Involved. |
| 21836 |
Site0002 |
F_0000046 |
7 |
2006-07-01 10:57:47.000 |
2006-07-01 10:57:47.000 |
|
|
|
|
service shortng under t2489 |
| 21837 |
Site0002 |
F_0000046 |
4 |
2006-07-01 13:23:19.000 |
2006-07-01 13:23:19.000 |
|
|
|
|
same service still shorting |
| 21838 |
Site0002 |
F_0000046 |
7 |
2006-07-01 13:33:10.000 |
2006-07-01 13:33:10.000 |
|
|
|
|
service finally smoked |
| 3929 |
Site0005 |
F_0000043 |
1 |
2006-07-05 05:02:48.000 |
2006-07-05 05:02:55.000 |
Equipment |
Unknown |
Sectionalizer |
Cable |
Equipment, Cable UG, Damaged. |
| 3931 |
Site0005 |
F_0000043 |
1 |
2006-07-05 05:59:40.000 |
2006-07-05 05:59:40.000 |
Equipment |
Unknown |
Sectionalizer |
Cable |
Equipment, Cable UG, Damaged. |
| 3934 |
Site0006 |
F_0000043 |
5 |
2006-07-05 09:47:51.000 |
2006-07-05 09:47:51.000 |
Equipment |
Unknown |
Sectionalizer |
Cable |
Equipment, Cable UG, Damaged. |
| 3933 |
Site0006 |
F_0000043 |
5 |
2006-07-05 09:47:51.000 |
2006-07-05 09:47:51.000 |
Equipment |
Unknown |
Sectionalizer |
Cable |
Equipment, Cable UG, Damaged. |
| 4004 |
Site0005 |
|
3 |
2006-07-14 11:11:07.000 |
2006-07-14 11:11:07.000 |
Unknown |
Unknown |
Unknown |
Unknown |
Unknown. |
| 4015 |
Site0011 |
F_0000007 |
2 |
2006-07-15 15:06:46.000 |
2006-07-15 15:07:30.000 |
Equipment |
Unknown |
Breaker |
Cable |
Equipment, Cable UG, Damaged. |
| 4016 |
Site0011 |
F_0000007 |
2 |
2006-07-15 15:06:46.000 |
2006-07-15 15:07:30.000 |
Equipment |
Unknown |
Breaker |
Cable |
Equipment, Cable UG, Damaged. |
| 4017 |
Site0011 |
F_0000007 |
2 |
2006-07-15 15:06:46.000 |
2006-07-15 15:07:30.000 |
Equipment |
Unknown |
Breaker |
Cable |
Equipment, Cable UG, Damaged. |
| 21839 |
Site0002 |
F_0000046 |
6 |
2006-07-16 06:03:01.000 |
2006-07-16 06:03:01.000 |
|
|
|
|
overloaded transformer in a three |
| 21840 |
Site0002 |
F_0000044 |
2 |
2006-07-18 14:40:36.000 |
2006-07-18 14:40:36.000 |
Animal |
|
|
|
live bird caused trans fuse to blo |
| 2889 |
Site0014 |
|
2 |
2006-07-18 19:07:37.000 |
2006-07-18 19:12:11.000 |
Tree |
Lightning |
Breaker |
|
Transmission Line tripped during a major storm. The cause of this event was likely tree contact. Breakers at Substations tripped and reclosed multiple times. |
| 2884 |
Site0010 |
|
2 |
2006-07-18 19:07:37.000 |
2006-07-18 19:12:11.000 |
Tree |
Lightning |
Breaker |
|
Transmission Line tripped during a major storm. The cause of this event was likely tree contact. Breakers at Substations tripped and reclosed multiple times. |
| 2883 |
Site0014 |
|
2 |
2006-07-18 19:07:37.000 |
2006-07-18 19:12:11.000 |
Tree |
Lightning |
Breaker |
|
Transmission Line tripped during a major storm. The cause of this event was likely tree contact. Breakers at Substations tripped and reclosed multiple times. |
| 2887 |
Site0014 |
|
2 |
2006-07-18 19:07:37.000 |
2006-07-18 19:12:11.000 |
Tree |
Lightning |
Breaker |
|
Transmission Line tripped during a major storm. The cause of this event was likely tree contact. Breakers at Substations tripped and reclosed multiple times. |
| 2880 |
Site0010 |
|
2 |
2006-07-18 19:07:37.000 |
2006-07-18 19:12:11.000 |
Tree |
Lightning |
Breaker |
|
Transmission Line tripped during a major storm. The cause of this event was likely tree contact. Breakers at Substations tripped and reclosed multiple times. |
| 2888 |
Site0010 |
|
2 |
2006-07-18 19:07:37.000 |
2006-07-18 19:12:11.000 |
Tree |
Lightning |
Breaker |
|
Transmission Line tripped during a major storm. The cause of this event was likely tree contact. Breakers at Substations tripped and reclosed multiple times. |
| 2878 |
Site0010 |
|
2 |
2006-07-18 19:07:37.000 |
2006-07-18 19:12:11.000 |
Tree |
Lightning |
Breaker |
|
Transmission Line tripped during a major storm. The cause of this event was likely tree contact. Breakers at Substations tripped and reclosed multiple times. |
| 2879 |
Site0014 |
|
2 |
2006-07-18 19:07:37.000 |
2006-07-18 19:12:11.000 |
Tree |
Lightning |
Breaker |
|
Transmission Line tripped during a major storm. The cause of this event was likely tree contact. Breakers at Substations tripped and reclosed multiple times. |
| 2882 |
Site0010 |
|
2 |
2006-07-18 19:07:37.000 |
2006-07-18 19:12:11.000 |
Tree |
Lightning |
Breaker |
|
Transmission Line tripped during a major storm. The cause of this event was likely tree contact. Breakers at Substations tripped and reclosed multiple times. |
| 2885 |
Site0010 |
|
2 |
2006-07-18 19:07:37.000 |
2006-07-18 19:12:11.000 |
Tree |
Lightning |
Breaker |
|
Transmission Line tripped during a major storm. The cause of this event was likely tree contact. Breakers at Substations tripped and reclosed multiple times. |
| 2881 |
Site0014 |
|
2 |
2006-07-18 19:07:37.000 |
2006-07-18 19:12:11.000 |
Tree |
Lightning |
Breaker |
|
Transmission Line tripped during a major storm. The cause of this event was likely tree contact. Breakers at Substations tripped and reclosed multiple times. |
| 2886 |
Site0014 |
|
2 |
2006-07-18 19:07:37.000 |
2006-07-18 19:12:11.000 |
Tree |
Lightning |
Breaker |
|
Transmission Line tripped during a major storm. The cause of this event was likely tree contact. Breakers at Substations tripped and reclosed multiple times. |
| 2890 |
Site0010 |
|
4 |
2006-07-18 19:43:14.000 |
2006-07-18 19:43:17.000 |
Lightning |
Lightning |
Breaker |
|
Lightning stroke causing several breakers to trip. |
| 2891 |
Site0014 |
|
4 |
2006-07-18 19:43:14.000 |
2006-07-18 19:43:17.000 |
Lightning |
Lightning |
Breaker |
|
Lightning stroke causing several breakers to trip. |
| 2892 |
Site0010 |
|
3 |
2006-07-18 22:49:29.000 |
2006-07-18 22:49:32.000 |
Lightning |
Lightning |
Breaker |
|
Two Lines tripped simultaneously causing a temporary outage at Bus #1. |
| 2893 |
Site0014 |
|
3 |
2006-07-18 22:49:29.000 |
2006-07-18 22:49:32.000 |
Lightning |
Lightning |
Breaker |
|
Two Lines tripped simultaneously causing a temporary outage at Bus #1. |
| 21841 |
Site0002 |
F_0000045 |
7 |
2006-07-19 13:54:39.000 |
2006-07-19 13:54:39.000 |
|
|
|
|
unknown as to what caused this |
| 4084 |
Site0005 |
F_0000038 |
7 |
2006-07-23 13:29:45.000 |
2006-07-23 13:29:45.000 |
Undetermined |
Heat |
Sectionalizer |
No Damage |
Undetermined. |
| 4083 |
Site0006 |
F_0000038 |
7 |
2006-07-23 13:29:45.000 |
2006-07-23 13:29:45.000 |
Undetermined |
Heat |
Sectionalizer |
No Damage |
Undetermined. |
| 4114 |
Site0012 |
F_0000036 |
2 |
2006-07-25 13:01:58.000 |
2006-07-25 13:01:58.000 |
Other |
Unknown |
Breaker |
Cable |
De-Energized For Safety, Other Connector UG, Contact - Damage. |
| 2899 |
Site0010 |
F_0000022 |
7 |
2006-07-28 15:54:57.000 |
2006-07-28 15:54:57.000 |
Lightning |
Lightning |
Breaker |
|
A lightning strike during a major storm caused primary down and tripped the circuit breaker. |
| 2904 |
Site0014 |
F_0000016 |
6 |
2006-07-28 18:41:06.000 |
2006-07-28 18:41:06.000 |
Lightning |
Lightning |
Breaker |
|
Lightning during a major storm caused primary wire to fall to the ground and trip the circuit breaker. |
| 21842 |
Site0002 |
F_0000044 |
1 |
2006-07-30 03:55:07.000 |
2006-07-30 03:55:07.000 |
Tree |
|
|
|
tree broke primary under n3177 |
| 21843 |
Site0002 |
F_0000044 |
2 |
2006-07-30 14:04:20.000 |
2006-07-30 14:04:20.000 |
|
|
|
|
replace ug elbow under n3395 |
| 2907 |
Site0010 |
F_0000026 |
2 |
2006-08-01 17:07:04.000 |
2006-08-01 17:08:53.000 |
Lightning |
Major Storm |
Recloser |
|
A lightning strike caused a recloser on F_0000026 to operate twice and caused primary wire to fall to the ground. |
| 2908 |
Site0010 |
F_0000026 |
4 |
2006-08-01 17:07:04.000 |
2006-08-01 17:08:53.000 |
Lightning |
Major Storm |
Recloser |
|
A lightning strike caused a recloser on F_0000026 to operate twice and caused primary wire to fall to the ground. |
| 2905 |
Site0010 |
F_0000026 |
2 |
2006-08-01 17:07:04.000 |
2006-08-01 17:08:53.000 |
Lightning |
Major Storm |
Recloser |
|
A lightning strike caused a recloser on F_0000026 to operate twice and caused primary wire to fall to the ground. |
| 2906 |
Site0010 |
F_0000026 |
2 |
2006-08-01 17:07:04.000 |
2006-08-01 17:08:53.000 |
Lightning |
Major Storm |
Recloser |
|
A lightning strike caused a recloser on F_0000026 to operate twice and caused primary wire to fall to the ground. |
| 2909 |
Site0010 |
F_0000024 |
3 |
2006-08-01 17:10:37.000 |
2006-08-01 17:10:37.000 |
Lightning |
Major Storm |
Recloser |
|
A lightning strike caused primary to fall to the ground and trip the circuit breaker of F_0000024. |
| 21844 |
Site0002 |
F_0000044 |
7 |
2006-08-01 19:13:23.000 |
2006-08-01 19:13:23.000 |
Tree |
|
|
|
tree brought service down causing |
| 2911 |
Site0014 |
|
2 |
2006-08-10 13:31:19.000 |
2006-08-10 13:31:19.000 |
Unknown |
|
Recloser |
|
No outage information found for this event. May have been a temporary fault cleared by a successful recloser operation per the sag duration. |
| 2912 |
Site0014 |
|
2 |
2006-08-10 14:25:00.000 |
2006-08-10 14:25:00.000 |
Unknown |
|
Recloser |
|
No outage information found for this event. May have been a temporary fault cleared by a successful recloser operation per the sag duration. |
| 2915 |
Site0014 |
|
5 |
2006-08-13 06:52:37.000 |
2006-08-13 06:52:38.000 |
Unknown |
|
Breaker |
|
A fault on Line caused the breaker to trip and reclose. The cause of this event is unknown and it's under investigation. |
| 2914 |
Site0010 |
|
5 |
2006-08-13 06:52:37.000 |
2006-08-13 06:52:38.000 |
Unknown |
|
Breaker |
|
A fault on Line caused the breaker to trip and reclose. The cause of this event is unknown and it's under investigation. |
| 4253 |
Site0006 |
|
7 |
2006-08-19 05:57:42.000 |
2006-08-19 05:57:42.000 |
Unknown |
Unknown |
Unknown |
Unknown |
Equipment, Cable UG, Damaged. |
| 21845 |
Site0002 |
F_0000046 |
3 |
2006-08-19 15:38:53.000 |
2006-08-19 15:38:53.000 |
Animal |
|
|
|
another animal attach under t3537 |
| 2918 |
Site0010 |
F_0000025 |
1 |
2006-08-20 05:40:31.000 |
2006-08-20 05:40:31.000 |
Equipment |
|
Breaker |
|
A fault on a Vac Pac Switch in Substation2 caused the circuit breaker of F_0000025 to trip. |
| 2919 |
Site0010 |
F_0000023 |
1 |
2006-08-20 11:01:38.000 |
2006-08-20 11:01:38.000 |
Equipment |
|
Switch |
|
A cable fault in the Substation tripped a Vac Pac Switch. This event is related to the earlier fault that occurred at Substation2 |
| 2920 |
Site0010 |
F_0000023 |
1 |
2006-08-20 18:25:53.000 |
2006-08-20 18:25:53.000 |
Equipment |
|
Switch |
|
A cable fault on primary cable feeding Substation2 from F_0000023 tripped a Vac Pac Switch. This event is related to the other two events from Site0010 this same day. |
| 4348 |
Site0005 |
F_0000040 |
7 |
2006-09-03 13:09:18.000 |
2006-09-03 13:09:18.000 |
Undetermined |
Unknown |
Breaker |
No Damage |
Undetermined. |
| 4373 |
Site0005 |
F_0000043 |
4 |
2006-09-06 15:26:19.000 |
2006-09-06 15:26:19.000 |
Equipment |
Unknown |
Fuse |
Other |
Equipment, Device UG, Damaged. |
| 21846 |
Site0002 |
F_0000044 |
6 |
2006-09-07 15:43:37.000 |
2006-09-07 15:43:37.000 |
Tree |
|
|
|
wind and trees cause this fuse to b |
| 21847 |
Site0002 |
F_0000046 |
7 |
2006-09-19 10:29:18.000 |
2006-09-19 10:29:18.000 |
|
|
|
|
arcing jumper under t7577 |
| 21848 |
Site0002 |
F_0000046 |
7 |
2006-09-19 10:32:16.000 |
2006-09-19 10:32:16.000 |
|
|
|
|
arching jumper |
| 21849 |
Site0002 |
F_0000046 |
7 |
2006-09-19 10:34:01.000 |
2006-09-19 10:34:01.000 |
|
|
|
|
arching jumper |
| 21850 |
Site0002 |
F_0000046 |
7 |
2006-09-19 10:35:45.000 |
2006-09-19 10:35:45.000 |
|
|
|
|
same jumper still arching |
| 21851 |
Site0002 |
F_0000046 |
7 |
2006-09-19 13:20:13.000 |
2006-09-19 13:20:13.000 |
|
|
|
|
last of srching jumper |
| 21852 |
Site0002 |
F_0000044 |
4 |
2006-10-01 07:14:05.000 |
2006-10-01 07:14:05.000 |
|
|
|
|
bad switch barrel t6293 |
| 2932 |
Site0014 |
F_0000018 |
4 |
2006-10-03 11:12:09.000 |
2006-10-03 11:12:09.000 |
Equipment |
|
Breaker |
|
A splice failure on F_0000018 out of Site0014 caused the circuit breaker to trip. |
| 21853 |
Site0002 |
F_0000044 |
2 |
2006-10-12 07:30:39.000 |
2006-10-12 07:30:39.000 |
|
|
|
|
unknown grimmlin caused this 10 am |
| 21854 |
Site0002 |
F_0000044 |
7 |
2006-10-19 16:44:30.000 |
2006-10-19 16:44:30.000 |
Tree |
|
|
|
bad weather blew down a tree that |
| 21855 |
Site0002 |
F_0000044 |
1 |
2006-10-30 08:21:57.000 |
2006-10-30 08:21:57.000 |
|
|
|
|
this overload transormer blew under |
| 2940 |
Site0014 |
F_0000012 |
2 |
2006-10-31 16:33:29.000 |
2006-10-31 16:33:45.000 |
Equipment |
|
Recloser |
|
A conductor off the pin on F_0000012 out of Site0014 Sub. caused a recloser to trip. |
| 2942 |
Site0014 |
F_0000012 |
3 |
2006-10-31 16:33:29.000 |
2006-10-31 16:33:45.000 |
Equipment |
|
Recloser |
|
A conductor off the pin on F_0000012 out of Site0014 Sub. caused a recloser to trip. |
| 2941 |
Site0014 |
F_0000012 |
2 |
2006-10-31 16:33:29.000 |
2006-10-31 16:33:45.000 |
Equipment |
|
Recloser |
Conductor |
A conductor off the pin on F_0000012 out of Site0014 Sub. caused a recloser to trip. |
| 4513 |
Site0006 |
F_0000039 |
2 |
2006-11-01 13:23:04.000 |
2006-11-01 13:23:04.000 |
Undetermined |
Unknown |
Service Restorer |
No Damage |
Undetermined. |
| 21856 |
Site0002 |
F_0000044 |
1 |
2006-11-02 05:03:53.000 |
2006-11-02 05:03:53.000 |
Tree |
|
|
|
wind and trees caused n3157 to blo |
| 2948 |
Site0014 |
|
4 |
2006-11-11 01:56:08.000 |
2006-11-11 01:56:08.000 |
Unknown |
|
Recloser |
|
Unknown cause. Possible successful recloser operation based on the event duration (4.5 cycles). |
| 2949 |
Site0010 |
|
5 |
2006-11-14 14:00:43.000 |
2006-11-14 14:00:46.000 |
Unknown |
|
Breaker |
|
While attempting to close back in transmission line a fault occurred trippint the a breaker at Substation. This event is under investigation. |
| 2950 |
Site0014 |
|
5 |
2006-11-14 14:00:43.000 |
2006-11-14 14:00:46.000 |
Unknown |
|
Breaker |
|
While attempting to close back in transmission line a fault occurred trippint the a breaker at Substation. This event is under investigation. |
| 21857 |
Site0002 |
F_0000044 |
1 |
2006-11-25 09:07:38.000 |
2006-11-25 09:07:38.000 |
|
|
|
|
closed transformer cutout |
| 4554 |
Site0011 |
F_0000008 |
1 |
2006-12-17 01:15:27.000 |
2006-12-17 01:15:49.000 |
Equipment |
Unknown |
Breaker |
Connector |
Equipment, Other Connector UG, Damaged. |
| 4553 |
Site0011 |
F_0000008 |
1 |
2006-12-17 01:15:27.000 |
2006-12-17 01:15:49.000 |
Equipment |
Unknown |
Breaker |
Connector |
Equipment, Other Connector UG, Damaged. |
| 4552 |
Site0011 |
F_0000008 |
1 |
2006-12-17 01:15:27.000 |
2006-12-17 01:15:49.000 |
Equipment |
Unknown |
Breaker |
Connector |
Equipment, Other Connector UG, Damaged. |
| 4556 |
Site0011 |
F_0000008 |
1 |
2006-12-17 03:58:27.000 |
2006-12-17 03:58:27.000 |
Equipment |
Unknown |
Breaker |
Connector |
Equipment, Other Connector UG, Damaged. |
| 2956 |
Site0014 |
|
3 |
2007-01-02 08:42:48.000 |
2007-01-02 08:42:48.000 |
Unknown |
Wind |
Breaker |
|
A phase to phase fault on the Transmission Line caused breakers at substations to trip and reclose. The cause of this event is unknown. |
| 2955 |
Site0010 |
|
3 |
2007-01-02 08:42:48.000 |
2007-01-02 08:42:48.000 |
Unknown |
Wind |
Breaker |
|
A phase to phase fault on the Transmission Line caused breakers at substations to trip and reclose. The cause of this event is unknown. |
| 21858 |
Site0002 |
F_0000044 |
7 |
2007-01-18 05:04:05.000 |
2007-01-18 05:04:05.000 |
|
|
|
|
cap bank on |
| 21859 |
Site0002 |
F_0000044 |
4 |
2007-01-18 05:18:07.000 |
2007-01-18 05:18:07.000 |
|
|
|
|
cap banl off |
| 21860 |
Site0002 |
F_0000046 |
6 |
2007-01-30 11:06:05.000 |
2007-01-30 11:06:05.000 |
|
|
|
|
t6501 A13808 customers lowside fau |
| 21861 |
Site0002 |
F_0000047 |
6 |
2007-02-07 11:17:34.000 |
2007-02-07 11:17:34.000 |
Vehicle |
|
|
|
truck hit pole breaker 1225 33rd s |
| 21862 |
Site0002 |
F_0000047 |
6 |
2007-02-07 11:18:15.000 |
2007-02-07 11:18:15.000 |
Vehicle |
|
|
|
truck hit pole 1225 33rd st shot3c |
| 21863 |
Site0002 |
F_0000047 |
7 |
2007-02-07 11:51:32.000 |
2007-02-07 11:51:32.000 |
Vehicle |
|
|
|
breaker reclose from truck hiting |
| 21865 |
Site0002 |
F_0000047 |
1 |
2007-02-07 11:59:03.000 |
2007-02-07 11:59:03.000 |
|
|
|
|
close phase A after pole repair. |
| 21864 |
Site0002 |
F_0000047 |
1 |
2007-02-07 11:59:03.000 |
2007-02-07 11:59:03.000 |
Vehicle |
|
|
|
truck hit pole sub breaker 1225 33. |
| 21866 |
Site0002 |
F_0000047 |
2 |
2007-02-07 11:59:13.000 |
2007-02-07 11:59:13.000 |
|
|
|
|
close another phase. |
| 21867 |
Site0002 |
F_0000047 |
4 |
2007-02-07 12:00:19.000 |
2007-02-07 12:00:19.000 |
|
|
|
|
close last phase after truck hit p. |
| 21868 |
Site0003 |
F_0000050 |
1 |
2007-03-22 09:59:08.000 |
2007-03-22 09:59:08.000 |
|
|
|
|
deteriorated line fuse. |
| 21869 |
Site0002 |
F_0000047 |
7 |
2007-04-13 09:17:28.000 |
2007-04-13 09:17:28.000 |
Animal |
|
|
|
t3521 100amp woodpecker attack. |
| 21870 |
Site0002 |
F_0000047 |
5 |
2007-04-13 10:56:27.000 |
2007-04-13 10:56:27.000 |
|
|
|
|
small motor start. |
| 2993 |
Site0014 |
|
1 |
2007-04-25 17:54:58.000 |
2007-04-25 17:57:32.000 |
Unknown |
|
Breaker |
|
A fault on Transmission Line caused breakers at Substations to trip. This event also led to relay overtrips on the other Lines. |
| 2994 |
Site0010 |
|
1 |
2007-04-25 17:54:58.000 |
2007-04-25 17:57:32.000 |
Unknown |
|
Breaker |
|
A fault on Transmission Line caused breakers at Substations to trip. This event also led to relay overtrips on the other Lines. |
| 2995 |
Site0014 |
|
2 |
2007-04-26 07:08:54.000 |
2007-04-26 07:08:54.000 |
Customer Caused |
|
Switch |
|
A fault at a customer switchgear caused a severe voltage sag at the substation bus at Site0014. The fault was cleared by the customer's switchgear. |
| 21871 |
Site0002 |
F_0000046 |
4 |
2007-05-11 01:41:13.000 |
2007-05-11 01:41:13.000 |
|
|
|
|
T8289 refused trans 10A rabbit att |
| 2997 |
Site0014 |
F_0000012 |
3 |
2007-05-16 16:15:33.000 |
2007-05-16 16:15:33.000 |
Equipment |
|
Breaker |
|
Bad potheads at a riser from F_0000012 out of Site0014 Substation caused the circuit breaker to trip. |
| 2998 |
Site0014 |
|
3 |
2007-05-16 17:30:50.000 |
2007-05-16 17:30:50.000 |
Unknown |
|
Unknown |
|
No outage information found for this event. |
| 2999 |
Site0014 |
F_0000017 |
7 |
2007-05-18 05:03:45.000 |
2007-05-18 05:03:45.000 |
Tree |
|
Breaker |
|
A tree contact on the mainline of F_0000017 from Site0014 Substation tripped the circuit breaker. |
| 21872 |
Site0002 |
F_0000044 |
1 |
2007-06-25 07:03:37.000 |
2007-06-25 07:03:37.000 |
|
|
|
|
n3157 bad arrester |
| 21873 |
Site0002 |
F_0000044 |
4 |
2007-07-09 10:49:01.000 |
2007-07-09 10:49:01.000 |
Animal |
|
|
|
anoher squirrel attack under t6293 |
| 21874 |
Site0002 |
F_0000044 |
1 |
2007-07-25 19:04:52.000 |
2007-07-25 19:04:52.000 |
|
|
|
|
arching |
| 21875 |
Site0002 |
F_0000044 |
4 |
2007-07-29 14:27:47.000 |
2007-07-29 14:27:47.000 |
|
|
|
|
more arching |
| 21876 |
Site0002 |
F_0000044 |
7 |
2007-07-29 19:18:07.000 |
2007-07-29 19:18:07.000 |
|
|
|
|
more arching |
| 21877 |
Site0003 |
F_0000050 |
4 |
2007-07-30 18:28:18.000 |
2007-07-30 18:28:18.000 |
|
|
|
|
t3527 10Amp tree limb. |
| 21878 |
Site0002 |
F_0000044 |
1 |
2007-07-31 13:18:56.000 |
2007-07-31 13:18:56.000 |
|
|
|
|
last of the arching |
| 21879 |
Site0002 |
F_0000047 |
1 |
2007-08-30 02:06:38.000 |
2007-08-30 02:06:38.000 |
|
|
|
|
t8937 100amp lightening strike. |
| 21880 |
Site0002 |
F_0000047 |
1 |
2007-08-30 04:11:34.000 |
2007-08-30 04:11:34.000 |
|
|
|
|
pick up load after lightning strik |
| 21881 |
Site0002 |
F_0000044 |
1 |
2007-09-29 06:31:55.000 |
2007-09-29 06:31:55.000 |
|
|
|
|
|